Sunday, May 26, 2013
Browse »
home»
motor
»
starting
»
Motor Starting
Motor Starting
The worked example here is a very simple power system with two voltage levels and supplied by a single generator. While unrealistic, it does manage to demonstrate the key concepts pertaining to motor starting calculations.
Step 1: Construct System Model and Collect Equipment Parameters
Simplified system model for motor starting example |
The power system has two voltage levels, 11kV and 415V, and is fed via a single 4MVA generator (G1). The 11kV bus has a standing load of 950kVA (S1) and we want to model the effects of starting a 250kW motor (M1). There is a standing load of 600kVA at 415V (S2), supplied by a 1.6MVA transformer (TX1). The equipment and cable parameters are as follows:
Equipment | Parameters |
---|---|
Generator G1 |
|
Generator Cable C1 |
|
11kV Standing Load S1 |
|
Motor M1 |
|
Motor Cable C2 |
|
Transformer TX1 |
|
Transformer Cable C3 |
|
415V Standing Load S2 |
|
Step 2: Calculate Equipment Impedances
Using the patameters above and the equations outlined earlier in the methodology, the following impedances were calculated:
Equipment | Resistance (Ω) | Reactance (Ω) |
---|---|---|
Generator G1 | 0.65462 | 9.35457 |
Generator Cable C1 | 0.00261 | 0.00413 |
11kV Standing Load S1 | 106.98947 | 69.10837 |
Motor M1 | 16.77752 | 61.02812 |
Motor Cable C2 | 0.1002 | 0.01725 |
Transformer TX1 (Primary Side) | 0.60027 | 4.49762 |
Transformer Cable C3 | 0.01176 | 0.00576 |
415V Standing Load S2 | 0.22963 | 0.17223 |
Step 3: Referring Impedances
11kV will be used as the reference voltage. The only impedance that needs to be referred to this reference voltage is the 415V Standing Load (S2). Knowing that the transformer is set at principal tap, we can calculate the winding ratio and apply it to refer the 415V Standing Load impedance to the 11kV side:
The resistance and reactance of the standing load referred to the 11kV side is now, R = 161.33333 Ω and X = 121.00 Ω.
Step 4: Construct the Equivalent Circuit
Equivalent circuit for motor starting example |
The equivalent circuit for the system is shown in the figure to the right. The "Near" Thevenin equivalent circuit is also shown, and we now calculate the equivalent load impedance in the steady-state condition (i.e. without the motor and motor cable impedances included):
Similarly the equivalent load impedance during motor starting (with the motor impedances included) can be calculated as as follows:
Step 5: Calculate the Initial Source EMF
"Near" Thevenin equivalent circuit for motor starting example |
Assuming that there is nominal voltage at the 11kV bus in the steady-state condition, the initial generator emf can be calculated by voltage divider:
-
- Vac
Step 6: Calculate System Voltages During Motor Start
Now we can calculate the transient effects of motor starting on the system voltages. Firstly, the current supplied by the generator during motor start is calculated:
Next, the voltage at the 11kV bus can be found:
-
- Vac (or 87.98% of nominal voltage)
The voltage at the motor terminals can then be found by voltage divider:
-
- Vac (or 87.92% of nominal voltage)
The voltage at the low voltage bus is:
-
- Vac, then referred to the LV side = 359.39Vac (or 86.60% of nominal voltage)
Any other voltages of interest on the system can be determined using the same methods as above.
Suppose that our maximum voltage drop at the motor terminals is 15%. From above, we have found that the voltage drop is 12.08% at the motor terminals. This is a slightly marginal result and it may be prudent to simulate the system in a software package to confirm the results.
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.